GX7600 Series Specifications
Chassis | |
---|---|
Input AC Power | 115 VAC @ 10 A, 50 / 60 Hz, or 230 VAC @ 5 A, 50 / 60 Hz Autorange switching |
Input Voltage Range | 90 VAC to 264 VAC rms |
Total Available DC Power | 550 W |
+5 V +3.3 V +12 V -12 V |
30 A (max) 30 A (max) 25 A (max) 5 A (max) |
Weight GX7600 GX7610 |
16 lbs 13 lbs |
Dimensions GX7600 / GX7610 |
4U (7″) H x 8.9″ W x 18″ D |
Cooling | Two 79 CFM fans for system cooling. Dedicated 50 CFM fan for power supply cooling. |
Temperature Monitoring | Integrated temperature monitoring via an on-board microcontroller with audible and software notification when preset temperature limits are exceeded. Per slot temperature monitoring, 1 reading/sec/slot 4 second moving average value User selectable alarm criteria:
Accuracy: ±2 °C |
Power Supply Monitoring | Monitored voltages: +3.3, +5, +12, -12, VIO value Accuracy: ±2% of reading |
PXI Triggers | Slots: 2 – 9 Number: 8 |
PXI Star Trigger | Slots: 2 – 9 Dedicated, low skew Star trigger connecting slots 2, 3, and 5 – 9 to slot 4, the PXIe system timing slot |
PXI Express DSTAR Triggers | Slots: 3, 4, and 5 3 dedicated differential pairs, connecting each PXI hybrid slot to the PXIe system timing slot |
PXI Clock and Synchronization Resources | Clocks: Integrated 10 and 100 MHz clock with an autodetect function. Presence of an external 10 MHz PXI clock will synchronize the 100 MHz clock to the external 10 MHz source 100 MHz clock accuracy: ±30 ppm Synchronization signals: SYNC100 & SYNC_CTRL |
External 10 MHz Clock Input | An external 10 MHz clock source (TTL level) can be provided via a rear panel BNC or via a PXI Express System Timing Controller |
10 MHz Clock Output | 10 MHz output is available via a rear panel BNC connector, TTL compatible level. |
Slots | 9 Slots (8 instruments max) 1 cPCIe controller slot 2 PXI Hybrid slots 5 PXI slots 1 PXIe System Timing slot |
GX7600, GX7602 Peripherals | DVD-RW and 160 GB (min) hard drive, 7200 rpm |
Environmental | |
---|---|
GX7600 / GX7610 Acoustic Noise (at operator level, 12 inches from front of unit) |
Auto fan setting (@ 23°C ambient): 58.4 dBA High fan setting: 61.3 dBA |
Operating Temperature | 0 °C to +50 °C |
Storage Temperature | -20 °C to +60 °C |
Emissions Compliance | EN55011:1991 Group 1 FCC Class A at 10 M |
CE Compliance | EN 61010-1 EN61326 |
Note: Specifications are subject to change without notice.